The 7100FP Fireplace will t a framed opening height of
45-7/8in.(1165mm)tallandwidthof42in.(1067mm).The
nishedcavitydepthmustbenolessthan24in.(610mm).
Framingmustextendstraightupallthewaytotheceiling.
Figure6.3showsatypicalframing(using2x4lumber)of
thereplace,assumingcombustiblematerialsareused.All
required clearances to combustibles around the replace
mustbeadheredto.SeeFigure6.2,onpreviouspage.Any
framingacross the topof thereplace must beabove the
levelofthetopstandoffs.(Norecessabovestandoffs.)
Figure 6.3 Framing the Fireplace
12 in.
(305mm)
42 in.
(1067mm)
45-7/8 in.
(1165mm)
24 in.
(610mm)
2 in.
(51mm)
Position
combustible/
non-combustible
mantel60in.
(1524mm)
frombaseof
thereplace
Non-combustible mantel material minimum height from
base of replace to underside of mantel 46 in. (1168mm)
when the following enclosure construction materials are
used:
Non-combustible framing materials must be used above
replace to height of 84 in. (2134mm) or to the ceiling
from base of replace for all construction materials,
framing members, sheeting, and all nish materials.
1. MINIMUM CLEARANCES TO COMBUSTIBLES
Materialswhichwillnotigniteandburn.Suchmaterialsare
thoseconsistingentirely ofsteel,iron, brick, tile,concrete,
slate,glassorplasters,oranycombinationthereof.
MaterialsthatarereportedaspassingASTME136,Stan-
dard Test Method for Behavior of Materials, in a Vertical
TubeFurnace at 750°C, shall beconsidered non-combus-
tiblematerials.
Materialsmadeoforsurfacedwithwood,compressedpa-
per,plantbers,plastics,orothermaterialsthatcanignite
andburn,whetherameproofedornot,orwhetherplastered
orun-plasteredshallbeconsideredcombustiblematerials.
3. NON-COMBUSTIBLE MATERIALS
4. COMBUSTIBLE MATERIALS
WITHIN ENCLOSURE AREA
Appliancetobackwall 1/2in.(13mm)
Appliancetosidewall 1in.(25mm)
Ductbootstoframing 0in.(0mm)
Topstandoffstoheader 0in.(0mm)
Dooropeningtosidewall 22-7/8in.(581mm)
EXPOSED SURFACES
Faceplatetosidewall 16in.(406mm)
Heatzoneairgrillstoceiling 12in.(305mm)
MANTEL
Mantelminimumheight 60in.(1524mm)
Maximummanteldepth 12in.(305mm)










Chimneysectionsatanylevelrequirea2in.(51mm)minimum
airspaceclearancebetweentheframingandchimneysection.
2. REDUCED MANTEL HEIGHT / OPTIONAL FRAMING
CONSTRUCTION REQUIRED:
5. CHIMNEY SECTIONS
C. Frame the Fireplace
 

